You may now think, that this is exactly what was offered as an option in the previous section, where we ruled it out, why repeat it now?
This is not so. Note, that in order to really change the classification of the area, we cannot merely study it again and again and hope to get a different answer every time. We will have to change the nature of that area, by reducing the hazards present. In the option that we are discussing now, we are not merely studying the classification again, we are going to physically change the characteristics of the classified area to make it safer.
In this case by having better ventilation of fresh air into the area.
For studying the second option, let us first study the basic idea behind area classification. The idea was to segregate areas, that were at risk of having explosive vapor or gas mixtures for longer periods of time, from other non hazardous areas. Again, further sub-dividing the hazardous areas into zones (Zone 0, Zone 1 and Zone 2) gives us finer choices, for selecting certain methods of protection over others, in a cost effective way. This is in keeping with the general principles of risk reduction, using ALARP (As Low As Reasonably Possible). This basically means, that we can spend truckloads of greenbacks on installing explosion protected equipment everywhere, even in safe areas, (to really really protect ourselves), but then the cost of doing so would drive us out of business. Thus we follow the ALARP principle.
For example, Increased Safety (Ex-e) as a method of protection, is allowed in Zone 2, but not in Zone 1. Thus we can have equipment that is appropriate for use in the area without overdesign or being unsafe.
However, what if we could continuously measure the so called hazardous area and check if there really are explosive gases or vapors present? Of course, we can and to do this correctly, we can install a fixed (not portable) combustible gas detector(s) in the hazardous area and monitor it in real time, if hazardous levels of vapors are present.
Option 2
You could install a combustible gas detector, that will detect the presence of combustible gas or vapor in the area and give warning alarms, or shut off the equipment immediately, in case flammable gas is detected.
Is this allowed? Yes of course, provided certain conditions are met. This protection method is known as "Combustible gas detector method of protection"
Conditions under which this method of protection may be used
Of course this method of protection is only allowed under certain conditions and not always, as it would completely defeat the very purpose of area classification. It would also dilute the safety of the installation if used recklessly. Broadly speaking, this method of protection should be used only under the following conditions:
1. If the area to be so protected has an area classification of a higher level (like Zone 1) only because of a lack of ventilation.
2. If the area is part of an industrial or work area which would have very little public access.
3. If fixed type combustible gas detectors are used to detect the presence of combustible mixtures of gas or vapors, in the same area, near which the equipment is sought to be installed.
4. The fixed combustible gas detector is itself certified to be used in the hazardous area under the same classification.
5. The fixed combustible gas detector is selected, installed and mounted as per prevailing standards and regulations.
6. The fixed combustible gas detector is regularly calibrated and tested for correctness of its indication, which means its integrity is never in question at any time.
7. The fixed combustible gas detector is capable of giving out a high level alarm signal (audio/visual) on detecting explosive levels of gas or vapor mixtures in the surroundings and this alarm or trip signal should also switch off the power to the equipment in the area.
8. The gas detector should cover the entire area which is sought to be protected.
The above are just broad guidelines and you should consult the appropriate national or international standards (or legal regulations), that apply to your installation.
Why not use it throughout the plant?
This method of protection cannot be used all over the plant. The reasons are many, but we enumerate a few below:
a) Modern plants may cover large land tracts. To cover this entire area (even just the hazardous areas) would require probably hundreds of fixed gas detectors. The costs of doing this would be huge. Again remember the ALARP principle.
b) The total cost of ownership also has to be considered. Each detector would have to have itself subject to periodic calibration & inspection, maintenance & repair.
c) It may not be practical to shut down entire plants just because of some gas leakages in certain portions of the plants.
d) Some equipment requires itself to be up and running, even in case of leakages or in presence of explosive gases or vapors. For example, alarm hooters, scrubber pumps, etc.
Conclusion
Merely having a higher level of area classification does not automatically preclude you from installing equipment of a lower area classification. A workaround for this situation is now available and consists of installing a suitable fixed type combustible gas detector, which continuously monitors the ambient air for any explosive or flammable levels of gas or vapor and takes adequate automatic alarm and trip actions to safely shut down the equipment in the hazardous area.
Further information
For further information on Hazardous Areas or Gas Monitors, please take a look at some excellent e-learning courses on these topics by us. These courses can be taken online at anytime and are very comprehensive.